7-9
IM 05P02C41-01EN
Input (PV
, Remote, and
Auxiliary
Analog) Functions
(2) Setting Square Root Extraction and Low Signal Cutoff Point
Description
This calculation is used to convert, for example, a differential pressure signal from a
throttling flow meter such as an orifice and nozzle into a flow-rate signal. There is no
hysteresis for low signal cutoff point.
Output = Input
The slope equals “1” at levels below
the low signal cutoff point (A.SR=1).
The slope equals “0” at levels below
the low signal cutoff point (A.SR=2).
Output
Input
Output = Input
Output
Input
Low signal cutoff
point is variable.
Low signal cutoff
point is variable.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
A.SR
PV analog input square root
extraction
PRO
OFF: No square root extraction.
1: Compute the square root.
(The slope equals “1.”)
2: Compute the square root.
(The slope equals “0.”)
PV
RSP analog input square
root extraction
PRO
RSP
AIN2 aux. analog input
square root extraction
PRO
AIN2
AIN4 aux. analog input
square root extraction
PRO
AIN4
A.LC
PV analog input low signal
cutoff
PRO
0.0 to 5.0%
PV
RSP analog input low signal
cutoff
PRO
RSP
AIN2 aux. analog input low
signal cutoff
PRO
AIN2
AIN4 aux. analog input low
signal cutoff
PRO
AIN4
Note 1: When each parameter is displayed, the terminal area (E1 to E4) is displayed on Group
display according to the suffix code and optional suffix code.
Note 2: Each parameter is displayed when the input type is voltage or current.
7
7.1 Setting Functions of PV Input, Remote Input, and Auxiliary Analog Input
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...