10-25
IM 05P02C41-01EN
Output (Control and Retransmission) Functions
10.15 Setting Split Computation Output Function
Description
Split computation output is useful for the case where multiple (up to 3) operating
units for switching, for example, hot and cool water are linked for control. There are
two characteristics of split computations: V-mode characteristics and Parallel-mode
characteristics. The current output range can be changed.
► Current output range: 10.14 Changing Current Output Range
V-mode Characteristics
The following explains an example of letting OUT terminal and RET terminal present the
V-mode characteristics of split computations.
Setting Example
OUT terminal
RET terminal
Control output type/Retransmission output type
OT = 00.02 (current)
RTS=OUT1
Current output 100% segmental point
OU.H=100.0%
RET.H=0.0%
Current output 0% segmental point
OU.L=25.0%
RET.L=75.0%
Current output range
OU.A=4-20
RET.A=4-20
0
50
25
75
100 %
%
mA
Output before split computation
Output after computation
OUT current output
100% segmental point
OUT current output
0% segmental point
RET current output
100% segmental point
RET current output
0% segmental point
RET terminal
25
0
50
75
100
20
4
3.8
12
8
16
OUT terminal
10
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...