9-44
IM 05P02C41-01EN
9.12 Program Pattern End Signal
Description
A pattern end signal notifies the outside of the end of a program pattern when the
execution of the program pattern ends.
The pattern end signal can be output by contact output or via communication.
There are one-second, three-second, and five-second pattern end signals.
When the program is also forcibly terminated by key operation, contact input, or via
communication, the pattern end signal is output. When the pattern-link function is used,
the pattern end signal is output when the link destination program pattern ends.
Even if program operation starts while the pattern end signal is on, the pattern end signal
is not turned off.
Setting Details
►
Pattern End Signal: 12.2 Setting Contact Output Function
Summary of Contents for UTAdvanced UP55A