18-13
IM 05P02C41-01EN
Parameters
18
Alarm Setpoint Setting Menu (Menu: AL)
Parameter
symbol
Name
Display
level
Setting range
Initial value
A1 to A8
Alarm-1 to -8
setpoint
EASY
These alarms work irrespective of
the operation mode.
Set a display value of setpoint of
PV alarm, SP alarm, deviation
alarm, output alarm, or velocity
alarm.
-19999 to 30000 (Set a value
within the input range.)
Decimal point position depends on
the input type.
0
In Cascade control, the following parameters are also displayed for secondary loop. (the LP2 lamp
is lit)
• Parameter: A1 to A8
SP-related Setting Menu (Menu: SPS)
Parameter
symbol
Name
Display
level
Setting range
Initial value
RMS
Remote input
method
STD
RSP: Via remote (aux. analog)
input
COM: Via communication
RSP
RFL
Remote input filter
STD
OFF, 1 to 120 s
OFF
RT
Remote input ratio
STD
0.001 to 9.999
1.000
RBS
Remote input bias
STD
-100.0 to 100.0% of PV input range
span (EUS)
0.0 % of PV
input range
span
SPT
SP tracking
selection
STD
OFF, ON
Tracking is performed when the
mode changes from Program
or Remote to Local. (The local
setpoint keeps track of the remote
setpoint.)
OFF
S.TM
Starting time of
program operation
STD
0.00 to 999.59 (“hour.minute” or
“minute.second” (common use of
instrument)
* Use the parameter TMU to set
the time unit.
0.00
PNC
Program pattern
number clearance
STD
OFF: Not cleared.
ON: Cleared. (Set the program
No. before restart program
operation)
* The controller resets (clears) the
program pattern number on the
operating display to “0” at the
end of program operation.
OFF
18.2 List of Parameters
Summary of Contents for UTAdvanced UP55A
Page 3: ......
Page 21: ...Blank Page ...
Page 37: ...Blank Page ...
Page 47: ...Blank Page ...
Page 125: ...Blank Page ...
Page 147: ...Blank Page ...
Page 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Page 221: ...Blank Page ...
Page 275: ...Blank Page ...
Page 351: ...Blank Page ...
Page 381: ...Blank Page ...
Page 403: ...Blank Page ...
Page 491: ...Blank Page ...
Page 505: ......
Page 513: ...Blank Page ...
Page 515: ...Blank Page ...