5 Outline of Motion Control Systems
5.1.1 DIP Switch Settings
5-2
5.1 Startup Sequence and Basic Operation
This section describes the MP2300 startup sequence and basic operation together with the DIP switch settings, self-
diagnosis at startup, and LED indicator patterns.
5.1.1 DIP Switch Settings
Set the DIP switch on the Basic Module to control operations of the startup sequence. The six switches are provided on
the DIP switch on the Basic Module as shown in the figure below. The following table lists the functions of six
switches.
SW1
OFF
ޓޓޓ
ON
STOP
SUP
INIT
CNFG
MON
TEST
123456
No.
Switch
Name
Status
Operating Mode
Default
Setting
Remarks
1
STOP
ON
User program stops
OFF
Set to ON to stop user program operation. Effective only at
power ON.
OFF
User program operation
2
SUP
ON
System use
OFF
Always set to OFF.
OFF
Normal operation
3
INIT
ON
Memory clear
OFF
Set to ON to clear memory.
Programs stored in flash memory will be run when Memory
Clear is set to OFF.
OFF
Normal operation
4
CNFG
ON
Configuration mode
OFF
Set to ON for self-configuration of connected devices.
OFF
Normal operation
5
MON
ON
System use
OFF
Always set to OFF.
OFF
Normal operation
6
TEST
ON
System use
OFF
Always set to OFF.
OFF
Normal operation