b3-19: Number of Speed Search Restarts
Sets the number of times the drive should attempt to find the speed and restart the motor using Speed Estimation Speed Search.
This function has no influence when Current Detection Speed Search is used (b3-24 = 0).
No.
Name
Setting Range
Default
b3-19
Number of Speed Search Restarts
0 to 10
3
n
b3-24: Speed Search Method Selection
Sets the Speed Search method used.
Note:
For explanations of the Speed Search methods,
Refer to Current Detection Type Speed Search (b3-24 = 0) on page 125
Estimation Type Speed Search (b3-24 = 1) on page 124
No.
Parameter Name
Setting Range
Default
b3-24
Speed Search Method Selection
0 or 1
0
Setting 0: Current Detection Speed Search
Setting 1: Speed Estimation Speed Search
n
b3-25: Speed Search Wait Time
Sets the wait time between Speed Search restarts.
No.
Name
Setting Range
Default
b3-25
Speed Search Wait Time
0.0 to 30.0 s
0.5 s
u
b4: Delay Timers
The timer function is independent of the drive operation and can be used to delay the switching of a digital output triggered
by a digital input signal. An On-delay and Off-delay can be separately set. The delay timer can help to get rid of chattering
switch noise from sensors.
To enable the timer function, a multi-function input must be set to “Timer input” (H1-
oo
= 18) and a multi-function output
must be set to “Timer output” (H2-
oo
= 12). Only one timer can be used.
n
b4-01/b4-02: Timer Function On/Off-Delay Time
b4-01 sets the On-delay time for switching the timer output. b4-02 sets the Off-delay time for switching the timer output.
No.
Name
Setting Range
Default
b4-01
Timer Function On-Delay Time
0.0 to 300.0 s
0.0 s
b4-02
Timer Function Off-Delay Time
0.0 to 300.0 s
0.0 s
n
Timer Function Operation
When the timer function input closes for longer than the value set in b4-01, the timer output switches on. When the timer
function input is open for longer than the value set in b4-02, the timer output function switches off. The following diagram
demonstrates the timer function operation.
b4-01
b4-02
b4-01
b4-02
Multi-function Contact
Input: Timer Function
On (Closed)
Off (Open)
On (Closed)
Off (Open)
Multi-function Contact
Output: Timer Function
ON
ON
ON
ON
Figure 5.17 Timer Operation
u
b5: PID Control
The drive has a built in PID (Propor In Derivative) controller that can be used for closed loop control of system
variables such as pressure, temperature etc. The difference between the target and the feedback value (deviation) is fed into
the PID controller. The PID controller adjusts the drive output frequency in order to minimize the deviation, providing an
accurate control of the system variables.