Drive Model
Non-time Delay
Fuse Rating (A)
Time Delay Fuses
Bussmann
Semiconductor
Fuse Part Number
Class J, T, or CC
Fuse Rating (A)
Class RK5
Fuse Rating (A)
Rating (A)
Minimum
Enclosure
Volume (in
3
)
2V0040
–
90
110
FWH-200B (200)
125
1152
2V0056
–
110
150
FWH-200B (200)
150
2560
2V0069
–
125
175
FWH-200B (200)
200
2560
400 V Class Three-Phase Drives
4V0002
6
3.5
3
FWH-40B (40)
15
1152
4V0004
15
7
8
FWH-50B (50)
15
1152
4V0005
20
10
10
FWH-70B (70)
15
1152
4V0007
25
12
15
FWH-70B (70)
20
1152
4V0009
25
15
20
FWH-90B (90)
20
1152
4V0011
30
20
30
FWH-90B (90)
35
1152
4V0018
–
35
45
FWH-80B (80)
50
1152
4V0023
–
40
50
FWH-100B (100)
60
1152
4V0031
–
60
80
FWH-125B (125)
90
1152
4V0038
–
70
90
FWH-200B (200)
110
1152
<1> Maximum 300% of drive input current rating for any Class J, T, or CC fuse except for models 4V0004, 4V0005, and 4V0007.
<2> Maximum 175% of drive input current rating for any Class J, T, or CC fuse.
<3> Maximum 225% of drive input current rating for any Class RK5 fuse.
<4> When using semiconductor fuses, Bussmann FWH are required for UL compliance.
<5> Maximum MCCB Rating is 15 A or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.
<6> Model 4V0004 requires Mersen (Ferraz) part number A6T15 for compliance.
<7> Model 4V0005 requires Mersen (Ferraz) part number A6T20 for compliance.
<8> Model 4V0007 requires Mersen (Ferraz) part number A6T25 for compliance.
n
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external
power supply shall be a UL-Listed Class 2 power source or equivalent.
Table D.16 Control Circuit Terminal Power Supply
Input / Output
Terminal Signal
Power Supply Specifications
Multi-function photocoupler output
P1, P2, PC
Requires class 2 power supply
Multi-function digital inputs
S1, S2, S3, S4, S5, S6, S7, SC
Use the internal power supply of the drive. Use class 2 for
external power supply.
Multi-function analog inputs
A1, A2, AC
Use the internal power supply of the drive. Use class 2 for
external power supply.
Pulse train input
RP
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
Pulse train output
MP
Use the internal LVLC power supply of the drive. Use class
2 for external power supply.
n
Drive Short-Circuit Rating
This drive has undergone the UL short-circuit test, which certifies that during a short circuit in the power supply the current
flow will not rise above 31,000 amps maximum at 240 V for 200 V class drives and 480 V for 400 V class drives.
• The MCCB and breaker protection and fuse ratings shall be equal to or greater than the short-circuit tolerance of the power
supply being used.
• Suitable for use on a circuit capable of delivering not more than 31,000 RMS symmetrical amperes for 240 V in 200 V class
drives (up to 480 V for 400 V class drives) motor overload protection.
D.1 UL Standards
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
439
D
Standards Compliance
Summary of Contents for iQpump Micro CIMR-PW Series