u
b6: Dwell Function
No.
(Addr.
Hex)
Name
Description
Values
Page
b6-01
(01B6) Dwell Reference at Start Dwell Ref @Start
Parameters b6-01 and b6-02 set the frequency to hold and the
time to maintain that frequency at start.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
b6-02
(01B7) Dwell Time at Start
Dwell Time @Start
Default: 0.0 s
Min.: 0.0
Max.: 10.0
b6-03
(01B8) Dwell Reference at Stop Dwell Ref @Stop
Parameters b6-03 and b6-04 set the frequency to hold and the
time to maintain that frequency at stop.
Default: 0.0 Hz
Min.: 0.0
Max.: 400.0
b6-04
(01B9) Dwell Time at Stop
Dwell Time @Stop
Default: 0.0 s
Min.: 0.0
Max.: 10.0