u
Writing to Multiple Registers
Function code 10h allows the user to write multiple drive MEMOBUS/Modbus registers with one message. This process works
similar to reading registers, i.e., the address of the first register that is to be written and the data quantity must be set in the
command message. The data to be written must be consecutive so that the register addresses are in order, starting from the
specified address in the command message. The data order must be high byte, then lower byte.
The following table shows an example of a message where a forward operation has been set with a frequency reference of
60.00 Hz for the slave 1 drive.
If parameter values are changed using the Write command, depending on the setting of H5-11, an Enter command will be
necessary to activate the data or save them.
Refer to H5-11: Communications Enter Function Selection on page 394
Refer to Enter Command on page 415
for detailed descriptions.
Command Message
Response Message (normal)
Response Message (fault)
Slave Address
01H
Slave Address
01H
Slave Address
01H
Function Code
10H
Function Code
10H
Function Code
90H
Starting No.
Upper
00H
Starting No.
Upper
00H
Error Code
02H
Lower
01H
Lower
01H
CRC-16
Upper
CDH
Data Quantity
Upper
00H
Data Quantity
Upper
00H
Lower
C1H
Lower
02H
Lower
02H
Number of Bytes
04H
CRC-16
Upper
10H
Starting Data
Upper
00H
Lower
08H
Lower
01H
Next Data
Upper
17H
Lower
70H
CRC-16
Upper
6DH
Lower
67H
Note:
For the number of bytes in the command message, take double the number of the data quantity.
C.9 Message Examples
400
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual