Table B.5 Three-Phase 400 V Class Drives Default Settings by Drive Capacity
No.
Description
Unit
Default Settings
−
Model
−
4V0002
4V0004
4V0005
4V0007
4V0009
o2-04
Drive Model Selection
Hex
92
93
94
95
96
E2-11
Motor rated power
kW
0.75
1.5
2.2
3.0
3.7
b3-06
Speed Search current 1
−
0.5
0.5
0.5
0.5
0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
–
0.5
0.5
0.5
0.5
0.5
C6-02
Carrier frequency
−
7
7
7
7
7
E2-01
Motor rated current
A
1.6
3.1
4.2
5.7
7
E2-02
Motor rated slip
Hz
2.6
2.5
3
2.7
2.7
E2-03
Motor no-load current
A
0.8
1.4
1.5
1.9
2.3
E2-05
Motor line-to-line resistance
Ω
22.459
10.1
6.495
4.360
3.333
E2-06
Motor leakage inductance
%
14.3
18.3
18.7
19
19.3
E2-10
Motor Iron Loss
W
26
53
77
105
130
L2-02
Momentary power loss ride-through time
s
0.1
0.2
0.3
0.5
0.5
L2-03
Momentary power loss Baseblock time
s
0.3
0.4
0.5
0.5
0.6
L2-04
Momentary power loss voltage recovery time
s
0.3
0.3
0.3
0.3
0.3
L2-05
Uv detection voltage
V dc
380
380
380
380
380
L3-24
Motor acceleration time
s
0.142
0.166
0.145
0.145
0.154
L8-02
Overheat alarm level
°C
110
110
90
100
100
L8-09
Ground fault selection
−
0
0
0
0
0
L8-38
Carrier frequency reduction selection
−
1
1
1
1
1
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
B.17 Defaults by Drive Model
380
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
Summary of Contents for iQpump Micro CIMR-PW Series
Page 443: ......