P4-23: Low City Off-Delay Time
Sets the amount of time a “Low City Pressure” condition must be absent before the drive will restart.
No.
Name
Setting Range
Default
P4-23
Low City Input Off-Delay Time
1 to 1000 s
5 s
n
P4-24: Low City Alarm Text
Selects the alarm message that will be displayed when a "Low City Pressure" condition is detected.
No.
Name
Setting Range
Default
P4-24
Low City Alarm Text
0 to 2
0
Setting 0: Low city pressure
Setting 1: Low suction pressure
Setting 2: Low water in tank
n
P4-25: Remote Drive Disable Selection
No.
Name
Setting Range
Default
P4-25
Remote Drive Disable Selection
0, 1
1
Setting 0: Normally open
When this parameter is set to 0 and digital input H1-0
o
= 95 (Remote Drive Disable) is closed for the time set in P4-26, Drive
Disable On-Delay, the drive will stop according to the method set in b1-03.
The drive will not run, and will display the “R-DNE-Sx” alarm where “Sx” denotes the digital input terminal programmed for
this function. For example, if H1-03 = 95, the alarm will display: “R-DNE-S3”.
To be able to run again, the Remote Drive Disable digital input has to be opened for the time set in P4-27, Drive Disable Off-
Delay.
Setting 1: Normally closed
When this parameter is set to 0 and digital input H1-0
o
= 95 (Remote Drive Disable) is opened for the time set in P4-26,
Drive Disable On-Delay, the drive will stop according to the method set in b1-03.
When drive run is disabled using this feature, the Pre-Charge function is reset and will run if necessary when drive run is
enabled.
n
P4-26: Remote Drive Disable On-Delay
Sets the amount of time a “Remote Drive Disable” condition must be present before the drive will stop.
No.
Name
Setting Range
Default
P4-26
Remote Drive Disable On-Delay
0 to 1000 s
0 s
n
P4-27: Remote Drive Disable Off-Delay
Sets the amount of time a “Remote Drive Disable” condition must be absent before the drive will be allowed to restart.
No.
Name
Setting Range
Default
P4-27
Remote Drive Disable Off-Delay
0 to 1000 s
0 s
n
P4-29: Lube Pump Message Text
Selects which text is displayed when Lube Pump is active. Also changes the text for the Lube Pump Digital Output selection
(H2-
oo
= 8B)
No.
Name
Setting Range
Default
P4-29
Lube Pump Message Text
0, 1
0
Setting 0: Lube Pump
Setting 1: Digital Out Delay
n
P4-30: Lube Pump Active During Run
When enabled, the Lube Pump digital output stays activated after the timer expires and the drive starts to run normally. The
output is deactivated only when the drive stops, faults, or sleeps.
5.11 P: Pump