Setting 0: Disabled
Setting 1: Enabled
n
Q3-11: Ripple Regulator Setpoint
Set as a percentage of the maximum amount of ripple allowed before an input phase loss fault is detected.
No.
Name
Setting Range
Default
Q3-11
Ripple Regulator Setpoint
0.0 to 200.0%
95.0%
u
S6: Drive Protection
n
S6-01: Emergency Override Speed
Sets the sped command used in emergency override mode when S6-02 = 0.
No.
Name
Setting Range
Default
S6-01
Emergency Override Speed
0.00 to 240.00 Hz
0.00 Hz
n
S6-02: Emergency Override Reference Selection
Selects the emergency override speed source.
No.
Name
Setting Range
Default
S6-02
Emergency Override Reference Selection
0, 1
0
Setting 0: Use S6-01 Reference
Setting 1: Use Frequency Reference
u
T: Motor Tuning
Auto-Tuning automatically sets and tunes parameters required for optimal motor performance.
Refer to T: Motor Tuning on page 368
for details on Auto-Tuning parameters.
5.12 Q: PID Controller
246
YASKAWA