When P9-12 is set to 2, the output frequency must also fall below the level set in P9-13.
No.
Name
Setting Range
Default
P9-14
Remove Delta Level
0.0 to 6000.0
0.0 PSI
n
P9-15: Remove Delay Time
Sets the delay time before the lead drive is removed from the system.
No.
Name
Setting Range
Default
P9-15
Remove Delay Time
0 to 3600 s
10 s
n
P9-16: Stabilization Time
Sets the time used to stabilize the system when a pump is staged or de-staged. Lead-lag control and pump protection is
suspended during this time.
No.
Name
Setting Range
Default
P9-16
Stabilization Time
0 to 3600 s
3 s
n
P9-17: Setpoint Modifier
The system setpoint is incremented with the P9-17 value depending on the number of pumps running.
Pump 1: Setpoint
Pump X: Se ((X-1) (P9-17))
No.
Name
Setting Range
Default
P9-17
Setpoint Modifier
-999.9 to 999.9
0.0 PSI
n
P9-18: High Feedback Quick De-Stage
Sets the feedback level to trigger a quick de-stage as a percentage of parameter P1-09.
No.
Name
Setting Range
Default
P9-18
High Feedback Quick De-Stage
0.0 to 100.0%
97.0%
The quick de-stage ignores parameters P9-12 to P9-15 and only uses an internal 2-second delay. A setting of 0.0 disables the
High Feedback De-stage feature.
n
P9-19: Alternation Unit
Selects the units for parameter P9-03, Alternation Time.
No.
Name
Setting Range
Default
P9-19
Alternation Unit
0, 1
0
Setting 0: Hours
Setting 1: Minutes
n
P9-20: Allow Network Run
No.
Name
Setting Range
Default
P9-20
Allow Network Run
0 to 3
0
Setting 0: Always
Allows the drive to respond to all network Run commands (first drive, staging, alternation).
Setting 1: First/Alternation
The drive is limited to being either the first drive or for alternation.
Setting 2: First only
The drive can only be a first drive.
5.11 P: Pump
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
241
5
Parameter Details