n
P9-32: Lag Follower Deceleration Time
Sets the deceleration time when the P9-33 timer is running and the drive is running as Lag Drive Speed Follower (P9-05 = 3).
No.
Name
Setting Range
Default
P9-32
Lag Follower Deceleration Time
0.0 to 1000.0 s
60.0 s
n
P9-33: Lag Follower Deceleration Time Active Time
Sets the window during which the P9-32 deceleration time is effective. The drive will use the standard deceleration rates when
the P9-32 time expires.
A setting of 0.0 will disable the Lag Follower deceleration time switching.
No.
Name
Setting Range
Default
P9-33
Lag Follower Deceleration Time Active Time
0.0 to 360.0 s
0.0 s
n
P9-34: Low Feedback Quick De-Stage
Sets the low feedback level that will trigger a quick de-stage. The quick de-stage ignores parameters P9-12 to P9-15 and uses
an internal 2-second delay.
A setting of 0.0 disables the Low Feedback De-Stage feature.
No.
Name
Setting Range
Default
P9-34
Low Feedback Quick De-Stage
0.0 to 6000.0
0.0 PSI
n
P9-99: Network Compatibility Selection
Selects the communication compatibility for the iQpump MEMOBUS network.
No.
Name
Setting Range
Default
P9-99
Network Compatibility Selection
0 to 2
0
Setting 0: A-Ver: 30034
Setting 1: B-Ver: 30035/36
Setting 2: iQ SmartNetwork