B.5 d: References
Reference parameters are used to set the various frequency reference values during operation.
u
d1: Frequency Reference
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
d1-01
(0280) Frequency Reference 1 Reference 1
Sets the frequency reference for the drive. Setting units are
determined by parameter o1-03.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-02
(0281) Frequency Reference 2 Reference 2
Frequency reference when digital input "Multi-Step Speed
Reference 1" (H1-
oo
= 3) is on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-03
(0282) Frequency Reference 3 Reference 3
Frequency reference when digital input "Multi-Step Speed
Reference 2” (H1-
oo
= 4) is on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-04
(0283) Frequency Reference 4 Reference 4
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2" (H1-
oo
= 3 and 4) are on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-05
(0284) Frequency Reference 5 Reference 5
Frequency reference when digital input "Multi-Step Speed
Reference 3" (H1-
oo
= 5) is on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-06
(0285) Frequency Reference 6 Reference 6
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 3 " (H1-
oo
= 3 and 5) are on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-07
(0286) Frequency Reference 7 Reference 7
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 3" (H1-
oo
= 4 and 5) are on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-08
(0287) Frequency Reference 8 Reference 8
Frequency reference when multi-function input "Multi-Step
speed reference 1, 2, 3" (H1-
oo
= 3, 4, 5) are on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-09
(0288) Frequency Reference 9 Reference 9
Frequency reference when multi-function input "Multi-Step
Speed Reference 4" (H1-
oo
= 32) is on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-10
(028B) Frequency Reference 10 Reference 10
Frequency reference when digital input "Multi-Step Speed
Reference 1, 4" (H1-
oo
= 3 and 32) are on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-11
(028C) Frequency Reference 11 Reference 11
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 4" (H1-
oo
= 4 and 32) are on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-12
(028D) Frequency Reference 12 Reference 12
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2, 4" (H1-
oo
= 3, 4, 32) are on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
d1-13
(028E) Frequency Reference 13 Reference 13
Frequency reference when digital inputs "Multi-Step Speed
Reference 3, 4" (H1-
oo
= 5 and 32) are on.
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
B.5 d: References
YASKAWA
TOEP YAIQPM 03B YASKAWA AC Drive - iQpump Micro User Manual
327
B
Parameter List
Summary of Contents for iQpump Micro CIMR-PW Series
Page 443: ......