EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
78
The SP-COP2-ENI module is a
General Purpose Discrete I/O Device.
For quick installation, use the
connection
Logic Output (1 to 400) and Logic/Physical Input
, if your PLC supports implicit messa-
ge transmission. The following figure shows the appropriate dialog in the Logix Designer.
Illustration 16: Basic connection selected in the Logix Designer
This connection comprises up to 50 bytes for data transmission from the PLC to the SP-COP2-ENI
module (assembly instance 37). This connection comprises up to 67 bytes for data transmission
from the SP-COP2-ENI module to the PLC (assembly instance 57). The following table offers an over-
view of these data bytes.
Table 38: Data of the class 1 connection “Logic output (1 to 400) and logic/physical input”
Instance
Byte
Access
Data type Description
Size
Data range
37
0 to 49
Write, read BYTE[50]
Output bytes, configuration via
Input data block 1 to 5
in
samosPLAN
6
1 to 50 Bytes
0 to 0xff
57
0 to 49
Read
BYTE[50]
Input bytes, configuration via
Output data block 1
in samos-
PLAN
6
1 to 50 Bytes
0 to 0xff
50 to 65
Read
BYTE[16]
Bits of the input terminals
(instance 401 to 528 of attribu-
te 3 class 8, currently not listed
in samosPLAN
6)
1 to 16 Bytes
0 to 0xff
66
Read
BYTE
Bit 7: Input state
Bit 6: Output state
(currently not listed in samos-
PLAN
6)
1 byte
0x00, 0x40,
0x80, 0xc0