Product description
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
19
Info
• You can find the module version on the type plate of the modules.
• You will find the samosPLAN
6 software version in the main menu.
• The latest software version is available in the Internet at the following address
http://www.wielandinc.com/.
• Newer modules are backwards-compatible, which means that each module can be replaced
with a module having a higher module version.
• You can find the date of manufacture for a device on the type plate in the
S/N
field in the format
<Product no.>yywwnnnnn (yy = year, ww = calendar week).
Equipment variants
77455755
There are three samosPRO gateways for various network types.
The Modbus TCP / PROFINET IO and EtherNet/IP gateway of the SP-COP2-ENI controller module or
the external SP-EN-ETC gateway are suitable for Ethernet networks. The SP-PROFIBUS-DP gateway
and the SP-CANopen gateway are external field bus gateways without an Ethernet function.
ATTENTION
Restrictions for Ethernet connections
• The Ethernet connection can only be linked to autonomous networks or demilitarized zones
(DMZ).
• The device must never be connected directly to the Internet.
• Always use secure data tunnels (VPN) to exchange data via the Internet.
Table 9: Equipment variants and their main characteristics
Gateway
Network type
Ethernet IP socket interface
SP-EN-MOD
Modbus TCP with master and
slave operation
Client/Server on TCP Port 502
SP-EN-PN
PROFINET IO device
UDP ports 34964, 49152
SP-EN-IP
EtherNet/IP device
TCP port 44818, UDP port 2222
SP-PROFIBUS-DP
PROFIBUS DP slave
- -
SP-CANopen
CANopen slave
- -
SP-EN-ETC
EtherCAT slave
- -
NOTICE
You will find the manufacturing date of a device on the type label in the S/N field in the format
yywwnnnn (yy = year, ww = calendar week, nnnn = sequential serial number within a calendar
week).
Data transferred to the network (network input data sets)
77477899
Available data
The samosPRO gateways can provide the following data:
• Process data
–
Logic results from
the samosPRO safety controller (see
Routing table [ch. 5.1.3, p. 43]
–
Input values
(HIGH/LOW) for all samosPRO input expansion modules in the system
–
Output values
(HIGH/LOW) for all samosPRO input/output expansion modules (see
state / input and output values [ch. 3.3.1, p. 24]
–
Output data
from another network, i.e. data received from a second gateway in the sa-
mosPRO system (see
Transmission of data from a second network [ch. 3.3.3, p. 25]
• Diagnostics
–
Test values
(CRCs): (see
Configuration test values (CRCs) [ch. 3.3.4, p. 25]
–
Error and state information
Error and state information for the modules [ch. 3.3.5, p. 26]
3.2
3.3