EtherCAT Gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
181
Error
Possible cause
Possible remedy
MS LED
/
Red / green
port, EtherCAT not active.
Init
state
LINK
(ETHERCAT-
IN)
Green
Controller errors
• Incorrect EtherCAT confi-
guration, gateway is
addressed with incorrect
data.
• Gateway is in
Pre-Op
state.
• Check network and device
configuration.
• Switch power off and back on.
MS LED
Red
RUN
Green /
flashing
ERR
Red /
flashing
LINK
Green
The SP-EN-ETC does not
provide any input data.
After switch-on:
• Gateway state is
Init
.
• Switch EtherCAT to
Op
state.
MS LED
/
Red / green
LINK
Green
LINK
Green
The SP-EN-ETC does not
provide any input data.
After switch-on:
• Gateway state is
Pre-Op
.
• Switch EtherCAT to
Op
state.
MS LED
/
Red / green
RUN
Green
LINK
Green
The SP-EN-ETC does not
provide any input data.
• Gateway state is
Safe-Op
. • Switch EtherCAT to
Op
state.
MS LED
/
Red / green
RUN
Green/flash
LINK
Green
The SP-EN-ETC does not
provide any input data.
• No EtherCAT data, but
there is a bus connection to
next EtherCAT slave.
• Re-start EtherCAT master or
supply master with power.
• Check RJ45 cable.
• Repair interruption to the
EtherCAT network.
MS LED
/
Red / green