EtherNet/IP gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
82
Illustration 22: Adding gateway data elements to the logic editor in samosPLAN
6 via drag & drop
Supported CIP Objects
79883019
Identity Object
79893259
The identity object is required for all EtherNet/IP-based products. Instance 1, attribute 1 stands for
the Vendor ID. Wieland Electric GmbH is listed by the ODVA using the value 314.
Instance 1, attribute 2 stands for the device types. The Open Type Code 0x07 stands for a
discrete
universal I/O device.
Instance 1, attribute 3 stands for the product code. It is of the type UNIT and thus comprises 2 bytes.
The decimal value is always constant at 1320.
Instance 1, attribute 4 stands for the revision, that means the main and supplementary firmware
version of the SP-COP2-ENI module, which you can find in the samosPLAN
6 software as the
Diag-
nostics version
. You can see both details in the
Properties
docking window, if you select the con-
troller module in the
Modules
docking window after you have connected to the station.
Illustration 23: Display of diagnostic version and hardware version in configuration dialog of the controller module
8.4
8.4.1