CANopen gateway
Wieland Electric GmbH | BA000970 | 07/2019 [9855]
158
Error
Possible cause
Possible remedy
MS LED
/
Red / green
× heartbeat producer time).
• Check the diagnostic mes-
sages with the aid of the
samosPLAN
6.
• Reset the samosPRO sys-
tem.
The SP-CANopen module is in
the critical error state
• Internal equipment error
on the SP-CANopen modu-
le.
• The module version of the
controller module does not
support samosPRO gate-
ways.
• Switch the samosPRO
system’s power supply off
and on again.
• Check the diagnostic mes-
sages with the aid of the
samosPLAN
6.
• Use the controller module
with the required module
version.
• If the error persists, replace
the gateway.
LED PWR
Green
LED NS
Red
MS LED
Red (2 Hz)
The SP-CANopen / the sa-
mosPRO system is in the
Criti-
cal error
state.
• The SP-CANopen module is
not properly connected to
the samosPRO modules.
• The module connection
plug is dirty or damaged.
• Another samosPRO module
has an internal critical er-
ror.
• Plug the SP-CANopen mo-
dule in correctly.
• Clean the connection plug
and socket.
• Switch on the power supp-
ly
• once again.
• Check the other samosPRO
modules.
LED PWR
Red
LED NS
Off
MS LED
Red