Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
81
IM-0882-03
1st Layer
2nd Layer
3rd Layer
(setting items)
4th Layer (setting values)
Remarks
Initial values
Settable values
4.System
General
Brightness
5 Bright
5Bright/4/3/2/1Dark/0 Off
Off means that whole of screen is turned off.
PowerOnDelay
None
None/2sec/5sec/10sec/20sec/30sec/60sec
Set time that until measure after power on.
PowerSavingTime
None
None/1/2/5/10/30/60min
Display is dark while power saving.
D-ZeroRetention
Disable
Disable/Enable
Whether remember D-Zero value or not.
Language
English
日本語
/English
Language.
DisplayDirection
Horizontal
Horizontal/Vertical
Select a direction of screen.
SettingProtect
Disable
Disable/Enable
AdjustProtect
Disable
Disable/Enable
Display
UpdateCycle
10 sps
1 sps/ 10 sps
PatternCopy
---
Go to screen of pattern copy.
Copy settings of pattern to other pattern.
AlarmLog
SyncedAlarm
AL1
:
ON
AL2
:
ON
AL3
:
ON
AL4
:
ON
AL1/AL2/AL3/AL4
RecordPos
BeforeAndAfter
BeforeAlarm/BeforeAndAfter/AfterAlarm
Overwrite
Enable
Disable/Enable
Initialize
UserDefaultSave
Save current settings as use initial values.
UserDefaultLoad
Initialize setting values to user initial values.
Factory
DefautLoad
Initialize setting values to factory default.
5.Diag/Log
InputDiag
DC InputA/B
ProcessInputA/B
-
InputRatingPercent
InputActualValue
Check input confirm existence.
Display percent value or actual value.
ExternalCtrl
-
-
Check ON/OFF of terminal.
OutputTest
Compare
AL1
~
AL4
-
-
Check ON/OFF Level of compare output.
PulseOutputA/B
-
-
Check ON/OFF Level of pulse output.
AnalogOutput
-
-
Output any value output.
(
Step by 10%
)
BCD
Output(Data)
-
-
Output ON/OFF data of each bits.
BCD Output(PC)
-
-
Output ON/OFF by photo coupler of each
bits.
ModbusCom
-
-
Display received and transmitted data.
RS-232C Com
-
-
Display received and transmitted data.
Alarm
LogView
No. 1
~
8
Go to screen of log data confirmation.
Alarm
LogClear
---
Erase alarm logs.