![WATANABE WPMZ-1 Instruction Manual Download Page 46](http://html1.mh-extra.com/html/watanabe/wpmz-1/wpmz-1_instruction-manual_3499830046.webp)
Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
45
IM-0882-03
11.
EXTERNAL CONTROL FUNCTION
OVERVIEW
As the external control function, the functions of "comparison reset", "hold (various types of hold)", "hold reset",
"digital zero", "pattern select", "switching measurement display", "trend log", etc. These functions can be
executed by assigning functions to external control terminals 1 to 5.
*In addition to terminal control, each external control can be assigned (registered) to 4 cross keys using the
shortcut function, and the assigned shortcut function can be executed by pressing and holding the key for 1
second on the measurement screen.
Setting of external control function is proceed as follow.
Each setting items about external control assignment are set up at [Setting]
⇒
[Input]
⇒
[ExternalCtrl]
⇒
[ExtCtrl1Func], [ExtCtrl2Func], [ExtCtrl3Func], [ExtCtrl4Func], [ExtCtrl5Func], and about hold function are
set up at [Setting]
⇒
[Input]
⇒
[HoldA], [HoldB]
* Each setting is saved and reflected at the timing of closing the menu and returning to the measurement screen.
Please note that the contents will not be saved if the power is turned off before closing the menu.
External control function list
The list of functions that can be assigned to external control is as follows.
Details of each function and setting will be described on the following pages after this section.
Function
Operation
None
None
CompareReset
Function to turn off all comparison output function
DispHoldA/B/A&B
Function to hold display value
MaxHoldA/B/A&B
Function to hold max value (Peak hold)
MinHoldA/B/A&B
Function to hold min value (Bottom hold)
AmpHoldA/B/A&B
Function to hold difference between max and min(Peak to peak
hold)
DevHoldA/B/A&B
Function to hold display value the most distant from reference
value
AveHoldA/B/A&B
Function to stabilize the display value by performing moving
average for the specified number of times
PatternSelect
HoldMode
*Set the items for hold function. If you do not use related holding
function, you do not need to set it.
DisoMode: Used with "DispHoldA, B, A&B" function
HoldOffDelay: Used with " DispHoldA, B, A&B " function
HoldMode: Used in each holding function
DevBaseValue: Used for "DevHoldA, B, A&B" function
AveHoldCount: Used with "AveHoldA, B, A&B" function
AveHoldCount
DevBaseValue
*Pattern registration is possible about hold function.
DispHoldMode
HoldOffDelay
External control
assignment
*Since external control assignment also includes
pattern control, patterns can not be registered.
【
Setting fot hold function
】