![WATANABE WPMZ-1 Instruction Manual Download Page 38](http://html1.mh-extra.com/html/watanabe/wpmz-1/wpmz-1_instruction-manual_3499830038.webp)
Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
37
IM-0882-03
Setting value:
1stInput : ±99999 (Default is 0)
1stOutput: ±99999 (Default is 0)
2ndInput: ±99999 (Default is 1000)
2ndOutput: ±99999 (Default is 1000)
・
・
・
15thInput: ±99999 (Default is 14000)
15thOutput: ±99999 (Default is 14000)
16thInput: ±99999 (Default is 15000)
16thOutput: ±99999 (Default is 15000)
DispShift
Set offset of display value.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[DispShift]
Setting value:
±99999(Default is 0)
TrackingZero
Tracking zero is a function that automatically corrects minute offset of display value over time. The judgment is
made at each setting time, and if the display value is within 0 ± “ActiveArea”, offset correction is performed and
the display value becomes 0.
While the tracking zero function is in operation, the "TZ" mark will light.
* The tracking zero function operates only when the digital zero function operates, and it works automatically
when the function is enabled and when the function of the digital zero function starts.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[TrackingZero]
Setting value:
Interval 0 to 9999[msec](Default is 0)
ActiveArea
±99999(Default is 0)
* If either of “Interval” or “ActiveArea” is 0, the tracking zero function is invalid.
* As the power is turned off, the offset value corrected by tracking zero becomes 0.
DispLimit
Sets the upper and lower limit of the display value. It is effective when you want to suppress output to 10 V even
if input is over (ex: 22mA) when input is 4 to 20 mA and output is 0 to 10 V.
ex) When the display value 0 to 10000 is set for the input 4-20 mA and the analog output is 0 to 10 V, the analog
output becomes maximum 10 V by setting the “UpperLimit” 10000. (The output is limited to 10 V even when an
excessive input of 22 mA is entered)
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[DispLimit]
Setting value:
LowerLimit ±99999 (Default is -99999)
UpperLimit
±99999(Default is +99999)
DispLoCut
It is a function to cut floating input near zero. If the absolute value of the display value is less than the set value,
set the display value to zero.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[DispLoCut]
Setting value: 0
~
99999 (Default is 0)
* Calculation processing of “DispLoCut” is performed after calculation processing of digital zero function.
InsDispStep
When the minimum digit of display value fluctuates, truncate the minimum digit and stabilize the display.