Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
80
IM-0882-03
1st Layer
2nd Layer
3rd Layer
(setting items)
4th Layer (setting values)
Remarks
Initial values
Settable values
2.Output
CompareList
---
---
Go to screen of CompareList
CompareAL1
CompareAL2
CompareAL3
CompareAL4
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
OutputDispValue
None
None/Ach/Bch/Calc
ActCondition
Always
Always/ExceptNearZero/OnStable
/ OnStableExceptNearZero/OnHold
Select a condition of comparison.
CompareMode
LevelJudge
LevelJudge/ZoneJudge/DiffJudge
OnConditions
Excess
Excess/LessThan
Only LevelJudge.
InTheZone
InTheZone/OutsideTheZone
Only ZoneJudge.
Threshold
10000
0
Threshold
:
±99999
Hysteresis
:
0
~
99999
Only LevelJudge.
0
10000
0
ZoneLowerLimit
:
±99999
ZoneUpperLimit
:
±99999
Hysteresis
:
0
~
99999
Only ZoneJudge.
10000
1.00
ChangeAmount
:
±99999
DetectionInterval
:
0.00
~
99.99[sec]
Only DiffJudge
OnDelay
None
None/20ms/50ms/100ms/200ms/500ms
1s/5s/10s/20s
Compare ON/OFF after ActCondition is kept
certain time set here.
OffDelay
None
OutputMode
Normal
Normal/Latch/OneShot5ms/10ms/20ms
/50ms/0.1s/0.2s/0.5s/1s/2s
Select an output mode.
OutputLogic
Negative(NO)
Positive(NC)/Negative(NO)
Select an output logic.
OnBgColors
Black
Black/Red/Yellow/Green
Priority: AL1 > AL2 > AL3 > AL4
Analog
Output
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
OutputRange
0-10V
0-10V/±10V/1-5V/0-20mA/4-20mA
Select a type of output range.
OutputDispValue
None
None/Ach/Bch/Calc
Select a ch referenced for analog output.
OutputScale
0
10000
0%
:
±99999
100%
:
±99999
Scaling of analog output.
Set 0% and 100% value.
BCD Output
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
OutputDispValue
None
None/Ach/Bch/Calc
Select a ch referenced for BCD output.
DataSignalLogic
Negative
Positive/Negative
Select an output mode.
SyncSignalLogic
Negative
Positive/Negative
Select an output mode.
ModbusCom
SlaveAddress
1
1
~
31
Set ID of the product.
Baudrate
19200bps
9600bps/19200bps/38400bps
Select a baudrate.
Parity
Even
None/Even/Odd
Select a type of parity bit.
RS-232C Com
Protocol
Modbus-RTU
ModbusRTU/OriginalCommand/OriginalO
utput
Select a protocol.
Baudrate
19200bps
9600bps/19200bps/38400bps
Select a baudrate.
Parity
Even
None/Even/Odd
Select a type of parity bit.
DataLength
7bit
7bit/8bit
Enable when Protocol is OriginalCommand
or OriginalOutput.
Stopbit
1bit
1bit/2bit
Enable when Protocol is OriginalCommand
or OriginalOutput.
Delimiter
CR LF
CR / CR LF
Enable when Protocol is OriginalCommand
or OriginalOutput.
3.Display
DispSelect
MeasureSelect
1ch product
Ach, Ach + Comp
Level, Trend
2ch product
Ach + Bch,
Level, Trend
Ach/Bch/Calc/Ach+Comp/Bch+Comp
/Calc+Comp/Ach+Bch/Calc+A+B
*Bch and Calc is enable in 2ch product.
LevelSelect
Ach/Bch/Calc/Ach+Bch
*Bch and Calc is enable in 2ch product.
TrendSelect
LevelDisp
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
Ach Scale
0
10000
LowerLimit
:
±99999
UpperLimit
:
±99999
Set scale of level screen.
Bch Scale
CalcScale
AL Select
AL1
~
AL4
:
ON
AL1/AL2/AL3/AL4
TrendDisp
PatternSelect
Pattern in use
Pattern 1/2/3/4/5/6/7/8
Select pattern No. to set.
Ach Scale
0
10000
LowerLimit
:
±99999
UpperLimit
:
±99999
Set scale of trend screen.
Bch Scale
CalcScale
AL Select
AL1
~
AL4
:
ON
AL1/AL2/AL3/AL4
TimeAxis
1s/div
100ms/div,1s/div,2s/div,5s/div,10s/div,
30s/div,60s/div120s/div
Set time scale of division time.