Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
26
IM-0882-03
Offset
Calibrate offset of input signal. Please calibrate both “Offset” and “Fullscale”.
●Operation for calibration (ex: InputRange 4-20mA, set display value to be 0-10000)
1. Select "Offset" and press "ENTER" key. (Go to offset setting screen)
2. Input 4mA to WPMZ and select "Read input val" and press "ENTER" key. Then, input current is
displayed in “Input”.
3. Set “Disp” to be “0”.
4. Back to forward screen by press “Left” key.
*You can also set “Input” manually.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[Offset]
Setting value:-99999
~
99999 (DispValue)
*Setting values of “DecPoint” and “DispUnit” are reflected.
(Default value is Disp:0 both DC input and process input.)
Fullscale
Calibrate fullscale of input signal. Please calibrate both “Offset” and “Fullscale”.
●Operation for calibration (ex: InputRange 4-20mA, set display value to be 0-10000)
1. Select "Fullscale" and press "ENTER" key. (Go to fullscale setting screen)
2. Input 20mA to WPMZ and select "Read input val" and press "ENTER" key. Then, input current is
displayed in “Input”.
3. Set “Disp” to be “10000”.
4. Back to forward screen by press “Left” key.
*You can also set “Input” manually.
Operation:[MENU]
⇒
[Input]
⇒
[DC InputA/B][ProcessInputA/B]
⇒
[FullScale]
Setting value:-99999
~
99999 (DispValue)
*Setting values of “DecPoint” and “DispUnit” are reflected.
(Default value is Disp:99999 when DC input, and Disp:10000 when process input.)