![WATANABE WPMZ-1 Instruction Manual Download Page 42](http://html1.mh-extra.com/html/watanabe/wpmz-1/wpmz-1_instruction-manual_3499830042.webp)
Graphical Digital Panel Meter WPMZ-1 INSTRUCTION MANUAL
41
IM-0882-03
*Examples of operation that ActCondition is OnHold and CompareMode is NormalHold or AreaHold are below.
Example: NormalHold and MaxHold
Example: AreaHold and MaxHold
OnDelay
This is a delay function that comparison output turns ON when the comparison condition is kept continuously
for the set time or more.
Operation:[MENU]
⇒
[Output]
⇒
[CompareAL1], [CompareAL2], [CompareAL3], [CompareAL4]
⇒
[OnDelay]
Setting value:
None(Default),20ms,50ms,100ms,200ms,500ms,1s,5s,10s,20s,
OffDelay
This is a delay function that comparison output turns OFF when the comparison condition is kept continuously
for the set time or more.
Operation:[MENU]
⇒
[Output]
⇒
[CompareAL1], [CompareAL2], [CompareAL3], [CompareAL4]
⇒
[OffDelay]
Setting value:
None(Default),20ms,50ms,100ms,200ms,500ms,1s,5s,10s,20s,
Conparison judgement is enable
ON
OFF
Input
Comparison output
Display Value
External control
Conparison judgement is enable
Update peak value
Hold peak value
ON
OFF
Input
Comparison output
Display Value
External control