Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
C5:20
Electronic minimum
flow temperature limit
20 °C
C5:1
to
C5:75
Minimum limit adjustable
from 1 to 75 °C
C6:74
Electronic maximum
flow temperature limit
74 °C
C6:10
to
C6:75
Maximum limit adjustable
from 10 to 75 °C
d3:14
Heating curve slope =
1.4
d3:2
to
d3:35
Heating curve slope ad-
justable from 0.2 to 3.5
(see page 54)
d4:0
Heating curve level = 0
d4:
–
13
to
d4:40
Heating curve level ad-
justable from
–
13 to 40
(see page 54)
d5:0
The external heating
mode changeover
switches the heating
program to "Constant
operation with reduced
room temperature"
d5:1
The external heating pro-
gram changeover
switches to "Constant
central heating with stan-
dard room temperature"
E1:1
With remote control: Set
day temperature is ad-
justable at the remote
control unit from 10 to
30 °C
E1:0
Set day temperature ad-
justable from 3 to 23 °C
E1:2
Set day temperature ad-
justable from 17 to 37 °C
E2:50
Heating with room tem-
perature hook-up must
be programmed for re-
mote control and for the
heating circuit: No dis-
play correction of the
actual room tempera-
ture
E2:0
to
E2:49
Display correction
–
5 K
to
Display correction -0.1 K
E2:51
to
E2:99
Display corr0.1 K
to
Display corr4.9 K
F1:0
Screed drying function
disabled (only for
weather-compensated
control units).
F1:1
to
F1:5
Screed drying function
adjustable in accordance
with five optional tem-
perature/time profiles
(see page 122)
F1:6
to
F1:15
Constant flow tempera-
ture 20 °C
Code 2
(cont.)
82
Coding
5592
883
GB
Summary of Contents for VITODENS 343-F WS4A
Page 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Page 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Page 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Page 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Page 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Page 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Page 151: ...151 5592 883 GB ...