If the burner control unit cannot be
reset after a fault shutdown, although
the boiler water temperature is below
approx. 75 °C, check the following:
1.
Pull the leads from
thermocouple
A
.
2.
Check the continuity of the thermo-
couple with a multimeter.
3.
Remove the faulty thermocouple.
4.
Install a new thermocouple.
5.
After commissioning, press reset
button "
E
RESET" at the control
unit.
Checking the fuse in the wiring chamber
1.
Switch OFF the power.
2.
Remove the cover from the wiring
chamber.
3.
Check fuse F1.
Repairs
(cont.)