Fault code
on the dis-
play
System character-
istics
Cause
Measures
9A
Control mode
Solar: Lead of the
collector tempera-
ture sensor S1 at
the Vitosolic bro-
ken
Check the sensor (see
page 102).
93
Control mode
Solar: Sensor S3
at the Vitosolic
shorted out
Check the sensor (see
page 102).
9b
Control mode
Solar: Lead of the
sensor S3 at the
Vitosolic broken
Check the sensor (see
page 102).
94
Control mode
Solar: Cylinder
temperature sen-
sor S2 at the
Vitosolic shorted
out
Check sensor.
9C
Control mode
Lead of the cylin-
der temperature
sensor S2 at the
Vitosolic broken
Check the sensor (see
page 102).
9F
Control mode
Solar control unit
fault message
See solar control unit
service instructions.
A6
Control mode
Impressed cur-
rent anode faulty;
no protective cur-
rent
Check impressed cur-
rent anode cable con-
tacts (see page 42)
A7
Control mode as per
delivered condition
Faulty program-
ming unit.
Replace the program-
ming unit.
b0
Burner blocked
Flue gas tem-
perature sensor
shorted out
Check the flue gas tem-
perature sensor (see
page 104).
b8
Burner blocked
Flue gas tem-
perature sensor
lead broken
Check the flue gas tem-
perature sensor (see
page 104).
b1
Control mode as per
delivered condition
Communication
fault; program-
ming unit (inter-
nal)
Check connections and
replace the program-
ming unit, if necessary.
Fault codes
(cont.)
94
Troubleshooting
5592
883
GB
Summary of Contents for VITODENS 343-F WS4A
Page 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Page 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Page 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Page 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Page 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Page 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Page 151: ...151 5592 883 GB ...