Checking the combustion quality
The electronic combustion control unit automatically ensures an optimum com-
bustion quality. Only the combustion values need to be checked during commis-
sioning and maintenance. For this, check the CO
2
or O
2
content. For a function
description of the electronic combustion control unit, see page 127.
CO
2
or O
2
content
The CO
2
content must be within the following ranges (upper and lower output):
&
7.7 to 9.2 % for natural gas E and LL
&
9.3 to 10.9 % for LPG P
For all gas types, the O
2
content must be between 4.4% and 6.9 %.
If the actual CO
2
or O
2
values lie outside their respective ranges, proceed with
the following steps:
&
Check the balanced flue system for soundness, see page 35.
&
Check the ionisation electrode and connecting cable, see page 38.
&
Check the parameters of the combustion control unit, see page 112.
Note
During commissioning, the combustion control unit carries out an automatic
calibration. This may lead to CO emissions in excess of 1000 ppm for a short
time.
1.
Connect a flue gas analyser at flue
gas port
A
on the boiler flue con-
nection.
2.
Open the gas shut-off valve, start
the compact boiler and create a
heat demand.
3.
Adjust the lower output.
&
Press both keys
9
and
d
simul-
taneously until the display shows
"Relay test".
&
With
a
/
b
in the display, select
"Base load".
Further details regarding the individual steps
(cont.)
45
Commissioning, inspection, maintenance
5592
883
GB
Service
Summary of Contents for VITODENS 343-F WS4A
Page 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Page 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Page 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Page 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Page 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Page 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Page 151: ...151 5592 883 GB ...