2.
d
to select heating circuit A1
(heating circuit without
mixer)
or
3.
a
"2
r
" flashes.
4.
d
to select heating circuit
with mixer M2.
5.
E
Call up the set night tem-
perature.
6.
a
/
b
Change the value.
7.
d
Confirm the value.
Connecting the control unit to the LON
The LON communication module
(accessories) must be plugged in.
Installation instructions
LON communication module
Note
The data transfer via LON can take
several minutes.
Single boiler system with Vitotronic 200-H and Vitocom 300
Set up the LON subscriber numbers
and further functions via code 2 (see
the following table).
Note
In the same LON system, the same
number
cannot
be allocated twice.
Only one Vitotronic
may be programmed as fault manager.
Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
Subscriber no. 1
Code "77:1"
Subscriber no. 10
Code "77:10"
Subscriber no. 11
Set
code "77:11"
Subscriber
no. 99
Control unit is fault
manager
Code "79:1"
Control unit is not
fault manager
Code "79:0"
Control unit is not
fault manager
Code "79:0"
Device is fault
manager
Control unit trans-
mits the time
Code "7b:1"
Control unit re-
ceives the time
Set
code "81:3"
Control unit re-
ceives the time
Set
code "81:3"
Device re-
ceives the
time
Further details regarding the individual steps
(cont.)
58
Commissioning, inspection, maintenance
5592
883
GB
Summary of Contents for VITODENS 343-F WS4A
Page 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Page 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Page 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Page 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Page 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Page 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Page 151: ...151 5592 883 GB ...