4.
Check the CO
2
content. Should the
actual value deviate by more than
1 % from the above range, imple-
ment the steps from page 45 (pos-
sibly replace the burner).
5.
Enter actual values into the service
report.
6.
Adjust the upper output.
&
With
a
/
b
in the display, select
"Full load".
7.
Check the CO
2
content. Should the
actual value deviate by more than
1 % from the above range, imple-
ment the steps from page 45 (pos-
sibly replace the burner).
8.
After testing, press
d
.
9.
Enter actual values into the service
report.
Further details regarding the individual steps
(cont.)
46
Commissioning, inspection, maintenance
5592
883
GB