Rated voltage:
230 V
–
Rated frequency:
50 Hz
Rated current:
6.3 A
Safety class:
I
Protection:
IP X 4 D to
EN 60529
Permissible ambient temperature
&
during operation:
0 to +40 °C
&
during storage
and transport:
-20 to +65 °C
Electronic tempera-
ture limiter setting:
82 °C
Temperature limiter
setting:
100 °C (fixed)
Line fuse (mains):
max. 16 A
Power consumption
&
Circulation
pumps:
max. 220 W
&
Burner:
max. 40 W
&
Control unit:
max. 10 W
Gas fired condensing compact boiler, category II
2ELL3P
Rated output range T
V
/T
R
50/30 °C
kW
4.2 to 13
Rated thermal load range
&
for central heating
&
for DHW heating
kW
kW
3.9 to 12.3
3.9 to 16.7
Connection values
relative to the max. load
with
Natural gas E
m
3
/h
1.77
Natural gas LL
m
3
/h
2.05
LPG
kg/h
1.31
Product ID
_
-0085 BO 0338
Note
The supply values are only for docu-
mentation purposes (e.g. in the gas
contract application) or to estimate
the supplementary volumetric set-
tings. Because of factory settings, the
gas pressure must not be altered from
these settings. Reference: 15 °C,
1013 mbar.
Specification
144
Specification
5592
883
GB
Summary of Contents for VITODENS 343-F WS4A
Page 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Page 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Page 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Page 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Page 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Page 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Page 151: ...151 5592 883 GB ...