Coding in the delivered condition
Possible change
84:0
Start capacity correc-
tion 0 %
84:
–
8
to
84:7
Start capacity correction
adjustable from -16 to
+14 %.
One step equals 2 %.
85:0
Standard mode
85:1
Manual calibration of the
combustion control unit.
The red fault indicator
also flashes during cali-
bration. The process has
terminated when the red
indicator no longer
flashes (after approx.
1 min). The air factor can
then be manually altered
in coding address "7d".
Note
Heat must be drawn off
during manual calibra-
tion.
Repairs
(cont.)
113
Troubleshooting
5592
883
GB
Service