The flue pipe is deemed to be sound if
the CO
2
concentration in the combus-
tion air is no higher than 0.2 % or the
O
2
concentration is at least 20.6 %.
If actual CO
2
values are higher or O
2
values are lower, then pressure test
the flue pipe with a static pressure of
200 Pa.
Removing the burner and checking the burner gasket
(replace gasket every two years)
1.
Switch OFF the main power supply
and the ON/OFF switch at the con-
trol unit.
2.
Close the gas shut-off valve and
safeguard against reopening.
3.
Pull electrical cables from fan
motor
A
, gas valve
B
, ionisation
electrode
C
, ignition unit
D
and
earth tab
E
.
4.
Undo the fixing screws of gas con-
nection flange
F
.
5.
Release four nuts
G
and remove
the burner.
!
Please note
Prevent damage to the wire
gauze.
Never rest the burner on the
gauze assembly.
Further details regarding the individual steps
(cont.)
36
Commissioning, inspection, maintenance
5592
883
GB