Coding in the delivered condition
Possible change
77 :1
LON subscriber number 77 :2
to
77 :99
LON subscriber number,
adjustable from 1 to 99:
1-4 = Compact boiler
5 = Never adjust
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only
once.
79:1
Control unit is fault
manager
79:0
Control unit is not fault
manager
7b:1
Send time via LON
7b:0
Do not send time via LON
7F:1
Detached house
7F:0
Apartment block
Separate adjustment of
holiday program and time
program for DHW heat-
ing, as option
80:1
With 5 s delay for fault
message; message is
displayed if fault is pre-
sent for at least 5 s
80:0
Without time delay
80:2
to
80:199
Time delay adjustable
from 10 to 995; 1 step =
5 s
81:1
Automatic summer/win-
ter time changeover
81:0
Manual summer/winter
time changeover
81:2
Radio clock module is
automatically detected
81:3
Accept time via LON
82:0
Operation with natural
gas
82:1
Operation with LPG (only
adjustable if coding ad-
dress 11:9 has been set;
see page 112)
88 :0
Temperature displayed
in °Celsius
88 :1
Temperature display in °
Fahrenheit
8A:175
Never adjust
90:128
Time constant for calcu-
lating the adjusted out-
side temperature
21.3 hours
90:0
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature,
subject to the set value
when the outside tem-
perature changes;
1 step = 10 min
Code 2
(cont.)
75
Coding
5592
883
GB
Service
Summary of Contents for VITODENS 343-F WS4A
Page 137: ...Parts lists cont 137 Parts lists 5592 883 GB Service ...
Page 138: ...Parts lists cont 138 Parts lists 5592 883 GB ...
Page 139: ...Parts lists cont 139 Parts lists 5592 883 GB Service ...
Page 140: ...Parts lists cont 140 Parts lists 5592 883 GB ...
Page 141: ...Parts lists cont 141 Parts lists 5592 883 GB Service ...
Page 142: ...Parts lists cont 142 Parts lists 5592 883 GB ...
Page 151: ...151 5592 883 GB ...