Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
63
9.
The display changes to "TESTING RELAY 1". Relay 1 is set to the alarm state and should turn in an alarm
for the time period previously set. Each relay is consecutively tested in this manner.
NOTE!
You can view your system's MCA Configuration Number by navigating to
"SPECNO#########" in the MCA "Inventory Menu".
List 10 MCA
(MCA Configuration Spec. No. 534876):
Relay #1 = Major Alarm
Relay #2 = Minor Alarm
Relay #3 = High Voltage 1 Alarm
Relay #4 = High Voltage 2 Alarm
Relay #5 = Battery On Discharge Alarm
Relay #6 = 50% Battery On Discharge Alarm
Relay #7 = AC Fail Alarm
Relay #8 = MCA Audible Alarm
Relay #9 = Test/Equalize Indication
List 11 MCA
(MCA Configuration Spec. No. 534877):
Relay #1 = Major Alarm
Relay #2 = Minor Alarm
Relay #3 = High Voltage 1 Alarm
Relay #4 = Rectifier Module Fail Major Alarm
Relay #5 = Battery On Discharge Alarm
Relay #6 = Rectifier Module Fail Minor Alarm
Relay #7 = AC Fail Alarm
Relay #8 = MCA Audible Alarm
Relay #9 = Fuse Alarm / Circuit Breaker Alarm
List 12 MCA
(MCA Configuration Spec. No. 534878):
Relay #1 = Major Alarm
Relay #2 = Minor Alarm
Relay #3 = High Voltage 1 Alarm
Relay #4 = MCA Fail Alarm
Relay #5 = Battery On Discharge Alarm
Relay #6 = Very Low Voltage Alarm
Relay #7 = AC Fail Alarm
Relay #8 = Fuse Alarm / Circuit Breaker Alarm
Relay #9 = Rectifier Module Fail Alarm
List 13 MCA
(MCA Configuration Spec. No. 534879):
Relay #1 = Major Alarm
Relay #2 = Minor Alarm
Relay #3 = Test/Equalize Mode 2
Relay #4 = Fuse Alarm / Circuit Breaker Alarm