Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
62
2.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE
MENU" is displayed.
3.
Press and release the FUNCTION SET ENTER pushbutton.
4.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "RELAYTEST =
###SEC" is displayed.
5.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The
"RELAYTEST =" portion of the display flashes.
6.
Observe the value displayed. Press and hold the FUNCTION SET YES (+) or NO (-) pushbutton until the
desired value is displayed. Release the pushbutton.
7.
With the desired value being displayed, press and release the FUNCTION SET ENTER pushbutton.
8.
“ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The
display stops flashing.
NOTE!
The relay test period will not be changed and the adjustment mode will be exited if the
FUNCTION SET YES (+) pushbutton is not pressed within 10 seconds of the “ARE YOU SURE? +
-”
prompt.
9.
To return to the beginning of the MCA Logic Tree, press and release the FUNCTION SET YES (+) and
NO (-) pushbuttons simultaneously.
Performing an Alarm Relay Test
Procedure
1.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Repeatedly press and release the FUNCTION SELECT DOWN
arrow pushbutton until "FUNCTION MENU" is displayed. Press and release the FUNCTION SET ENTER
pushbutton.
2.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT
MENU" is displayed.
3.
Press and release the FUNCTION SET ENTER pushbutton.
4.
Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "ADJUST ALARMS".
5.
Press and release the FUNCTION SET ENTER pushbutton.
6.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "TEST ALM
RELAYS" is displayed.
7.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
8.
“ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton.