Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
30
MCA
Menu
Tree
Line No.
(Section
6022)
Message Displayed
Associated
with...
Definition
Can this value
be changed?
77
RELAYTEST = ###SEC
Configure
Menu
Sets the Alarm Relay Test feature's
time period.
Yes, see
"System
Operating
Procedures".
77A
SET SPANISH TEXT
Configure
Menu
Sets the text to spanish.
Yes
78
FUNCTION MENU
Configure
Menu
Moves you back to this menu.
No
79
NORMAL DISPLAY
Configure
Menu
Moves you to the beginning of the
MCA Menu Tree. "SYSTEM OK" or
"## ALARMS ACTIVE" is displayed.
No
80
CAL SYS = ###.##V
Calibration
Menu
Allows calibration of the display
meter for system output voltage
reading.
Yes, see "MCA
System
Adjustments".
81
CAL SUB = ###.##V
Calibration
Menu
Allows calibration of the display
meter for subsystem output voltage
reading.
Yes, see "MCA
System
Adjustments".
82
RESTORE MFG CAL
Calibration
Menu
Returns system voltage calibration
and subsystem voltage calibration
values back to their factory defaults.
When the "CAL SYS" or "CAL SUB"
setting has been changed, the
setting can be returned to its default
value by performing this operation.
Yes, see "MCA
System
Adjustments".
83
ANALOG TC OFF
or
TC CAL = ##.##V
or
TempCmp Hardware
Calibration
Menu
not used in this system
--
83A
DIGITAL TC OFF
or
SLOPE = .###V/ºC
or
TempCmp Hardware
Calibration
Menu
Allows adjusting the system to
operate with a battery charge
temperature compensation probe or
disabling the feature.
or
The user tried to set the SLOPE
value when a temperature
compensation module was also
present.
Yes, see "MCA
System
Adjustments".