Returning System and Subsystem Output Voltage Reading Calibrations to their Default
Values
Local MCA Control Panel Adjustment Procedure
1.
All controls are located on the MCA Interface Pad. Refer to
2.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Repeatedly press and release the FUNCTION SELECT DOWN
arrow pushbutton until "FUNCTION MENU" is displayed. Press and release the FUNCTION SET ENTER
pushbutton.
3.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION
MENU" is displayed.
4.
Press and release the FUNCTION SET ENTER pushbutton.
5.
Press and release the FUNCTION SELECT DOWN arrow pushbutton until "SET FACTORY CAL." is
displayed.
NOTE!
If the calibration values are at their defaults, this option is not displayed.
6.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
7.
"ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
NOTE!
The system and subsystem output voltage reading calibration values will not change to their
defaults and the calibration mode will be exited if the FUNCTION SET YES (+) pushbutton is not
pressed within 10 seconds of the “ARE YOU SURE? +
-” prompt.
8.
Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the
beginning of the MCA menu tree.