Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until the low voltage
disconnect circuit to be reconnected is displayed ("RECONNECT LVD**", **=the designation of the low
voltage disconnect circuit).
6.
To reconnect the low voltage disconnect circuit being displayed, press and release the ALARM CUTOFF
and FUNCTION SET ENTER pushbuttons simultaneously.
7.
"ARE YOU SURE? +-" is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The low
voltage disconnect circuit reconnects.
8.
If the system contains additional low voltage disconnect circuits, separately reconnect these by
repeating steps 5) through 7).
9.
When done, press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously.
You are returned to the beginning of the MCA menu tree.
Setting Low Voltage Disconnect (IF FURNISHED) for Manual Reconnect
The low voltage disconnect circuit is set for automatic reconnect when a value is selected for the Low Voltage
Disconnect "Reconnect" value.
The low voltage disconnect circuit is set for manual reconnect when "MANUAL RECONNECT" is selected as the
Low Voltage Disconnect "Reconnect" value, as outlined below.
Procedure
1.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Repeatedly press and release the FUNCTION SELECT DOWN
arrow pushbutton until "FUNCTION MENU" is displayed. Press and release the FUNCTION SET ENTER
pushbutton.
2.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUSTMENT
MENU" is displayed.
3.
Press and release the FUNCTION SET ENTER pushbutton.
4.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "ADJUST LVD" is
displayed.
5.
Press and release the FUNCTION SET ENTER pushbutton.
6.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "LVRECON =
##.##V" is displayed.
NOTE!
If "MANUAL RECONNECT" is displayed, low voltage disconnect is already set for manual
reconnect. In this case, proceed with step 11).
7.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The
"LVRECON =" portion of the display flashes.