Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
47
Manual Battery Disconnect Switch and Indicator (List RB, RC, RD Only)
Table 3:
Manual Battery Disconnect Control and Indicator
Control / Indicator
Description
NORM/DISC
(Normal/Disconnect
Switch)
•
DISC
(Disconnect Switch
Position)
•
NORM
(Normal Switch Position)
This is a locking type toggle switch. To operate switch, pull out switch
handle and move handle left or right to desired position. Release handle to
lock into new position.
•
Placing the switch in this position causes the associated contactor to
open, thus disconnecting battery from the power system and loads.
•
Returning the switch to this position reconnects battery to the power
system and loads.
BAT DISC
(Battery Disconnect Indicator)
Illuminates red if the NORM/DISC battery disconnect switch is placed in the
DISC position.