Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
31
MCA
Menu
Tree
Line No.
(Section
6022)
Message Displayed
Associated
with...
Definition
Can this value
be changed?
83B
MAX W/T = ##.##V
Calibration
Menu
Displays maximum voltage with
temperature compensation set point.
Yes, see "MCA
System
Adjustments".
83C
MIN W/T = ##.##V
Calibration
Menu
Displays minimum voltage with
temperature compensation set point.
Yes, see "MCA
System
Adjustments".
83D
TCOMP ON SENSOR1
or
TCOMP ON AVERAGE
or
TCOMP ON HIGHEST
Calibration
Menu
Selects the temperature
compensation source. Options are
'SENSOR1' when only one
temperature probe is used, or
'AVERAGE' or 'HIGHEST' when
multiple probes are used.
Yes, see "MCA
System
Adjustments".
84
FUNCTION MENU
Calibration
Menu
Moves you back to this menu.
No
85
NORMAL DISPLAY
Calibration
Menu
Moves you to the beginning of the
MCA Menu Tree. "SYSTEM OK" or
"## ALARMS ACTIVE" is displayed.
No
86
SYSLOAD** #####A
System
Load Menu
Displays individual load current
through a system shunt.
** = designation of the system load
shunt.
#### = value.
No
87
MEASUREMENT MENU
System
Load Menu
Moves you back to this menu.
No
88
NORMAL DISPLAY
System
Load Menu
Moves you to the beginning of the
MCA Menu Tree. "SYSTEM OK" or
"## ALARMS ACTIVE" is displayed.
No
89
PCU** LOAD #####A
PCU
Load Menu
Displays individual Rectifier Module
(PCU) Load Current
** = designation of the Rectifier
Module (PCU).
#### = value.
No
90
MEASUREMENT MENU
PCU
Load Menu
Moves you back to this menu.
No
91
NORMAL DISPLAY
PCU
Load Menu
Moves you to the beginning of the
MCA Menu Tree. "SYSTEM OK" or
"## ALARMS ACTIVE" is displayed.
No