Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
152
f)
At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton to store the new
value, or the FUNCTION SET NO (-) pushbutton to cancel this operation without changing the
setting.
g)
Display the next or previous entry using the FUNCTION SELECT UP or DOWN arrow pushbutton.
h)
Repeat this procedure for each entry presented.
7.
When all the adjustable values have been properly set, press the FUNCTION SELECT DOWN arrow
pushbutton until "START THE SYSTEM" is displayed.
8.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
9.
At the "ARE YOU SURE? +-" prompt, press the FUNCTION SET YES (+) pushbutton.
10.
The MCA briefly displays "INITIALIZING..." along with the maximum remaining initialization time in
seconds while it is starting the system.
CHECK SETPOINTS Adjustable Values
1.
FLOAT = ##.##V
##.##V = float voltage setting for all Rectifier Modules
2.
TEST/EQ = ##.##V
##.##V = test equalize voltage setting for all Rectifier Modules
3.
SET HVS = ##.##V
##.##V = high voltage shutdown setting for all Rectifier Modules
4.
CURRLIM = #####A
CURRLIM = #####MAX
#####A = system current limit setting, current limit circuit on all Rectifier Modules are automatically
adjusted to ensure system current does not exceed this value
#####MAX = the sum of the maximum capabilities of all Rectifier Modules installed in the system
5.
SYS HV1 = ##.##V
##.##V = system high voltage alarm 1 setting
6.
SYS HV2 = ##.##V
##.##V = system high voltage alarm 2 setting
7.
SYS BOD = ##.##V
##.##V = system battery on discharge alarm setting
8.
SYS 50% (VERYLOVOLT) = ##.##V
##.##V = system 50% battery on discharge (very low voltage) alarm setting
9.
SYSCURR = #####A
####A = system current alarm setting
10.
SUB HV = ##.##V
##.##V = subsystem high voltage alarm setting
11.
SUB LV = ##.##V
##.##V = subsystem low voltage alarm setting