Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
136
Table 6:
MCA Basic Settings
BASIC SETTINGS
Setting
Factory
Default Setting
MCA Config.
534876, 534878,
and 534879
Factory
Default Setting
MCA Config.
534877
Required
Site Setting
Float Voltage
27.24V
27.00V
Test/Equalize Voltage
27.24V
27.50V
High Voltage Shutdown
28.75V
28.50V
System Current Limit
100% of Rated
Full Load
100% of Rated
Full Load
System HV1
27.75V
28.10V
System HV2
28.25V
28.50V
System BOD
24.00V
23.50V
System 50%BOD
23.00V
22.00V
System Current Alarm
2000A
2000A
Subsystem HV
50.00V
53.00V
Subsystem LV
46.00V
44.50V
Subsystem Current Alarm
2000A
2000A
LVD 1A
21.0V
21.7V
LVD 1B
21.0V
21.7V
LVD 2A
21.0V
21.7V
LVD 2B
21.0V
21.7V
LVD 3A
21.0V
21.7V
LVD 3B
21.0V
21.7V
LVD Reconnect
24.5V
25.2V
Digital Temperature
Compensation (Slope)
Off (0V/
°
C)
Off (0V/
°
C)
Digital Temperature
Compensation (MAX W/T)
28.25V
28.00V
Digital Temperature
Compensation (MIN W/T)
25.00V
25.70V
Temperature Compensation Source
TCOMP ON
SENSOR1
TCOMP ON
SENSOR1
High Battery Ambient
Temperature Alarm
Off
Off
Low Battery Ambient
Temperature Alarm
Off
Off
Number of Available
Rectifier Module Mounting Positions
-
-