Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
119
Figure 3:
Handle/Latch Mechanism on the Rectifier or DC-DC Converter Module
Procedure
1.
Unpack the module.
2.
Note the model number located on the handle of the module. Model numbers starting with the letter “R”
(R24-2500 or R24-3000) are Rectifier Modules (PCUs). Model numbers starting with the letter “C”
(C2448-1500) are DC-DC Converter Modules.
3.
Check the module location diagram on the front of the shelf to determine which type of module
(Rectifier or DC-DC Converter) can be installed in each mounting position. See
4.
If present, remove blank cover panel from the mounting position into which Rectifier or DC-DC
Converter Module is to be installed.
5.
Place the module into the unoccupied mounting slot without sliding it in completely.
6.
Loosen the captive screw on the module handle. Pull the handle to pivot it out of the module front panel
(this will also retract the latch mechanism located at the right side of the module).
7.
Push the module completely into the shelf.
8.
Push the handle into the front panel of the module. This will lock the module securely to the shelf.
Tighten the captive screw on the handle.
9.
After the module is physically installed in the mounting shelf, it is ready for operation immediately after
power is supplied to it.
Captive
Screw
Handle in
Closed Position
Note: Handle must be
open when installing
or removing module.