68
4.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "EMERG STOP
ON" or " EMERG STOP OFF" is displayed. This is the current setting for this feature. To toggle this
setting, perform steps 5) through 7). To keep this setting, proceed with step 7).
5.
To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons
simultaneously.
6.
"ARE YOU SURE? +_" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7.
Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the
beginning of the MCA menu tree.
Setting the MCA Remote High Voltage Shutdown Feature
The MCA can be set to enable or disable the Remote High Voltage Shutdown feature. When the feature is
disabled, application of an external high voltage shutdown signal has no effect on the system.
Enabling or Disabling the ' Remote High Voltage Shutdown ' Feature
Procedure
1.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Repeatedly press and release the FUNCTION SELECT DOWN
arrow pushbutton until "FUNCTION MENU" is displayed. Press and release the FUNCTION SET ENTER
pushbutton.
2.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE
MENU" is displayed.
3.
Press and release the FUNCTION SET ENTER pushbutton.
4.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until " REMOTE HVS
ON" or " REMOTE HVS OFF" is displayed. This is the current setting for this feature. To toggle this
setting, perform steps 5) through 7). To keep this setting, proceed with step 7).
5.
To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons
simultaneously.
6.
"ARE YOU SURE? +_" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7.
Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the
beginning of the MCA menu tree.