Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
154
Advanced Settings
Set the following to the settings recorded in
Procedure
1.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
2.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE
MENU" is displayed.
3.
Press and release the FUNCTION SET ENTER pushbutton.
4.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "DISPLAY ROLL
OFF" or "DISPLAY ROLL ON" is displayed. This is the current setting for this feature. To toggle this
setting, perform steps 5) and 6). To keep this setting, proceed with step 7).
5.
To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons
simultaneously.
6.
"ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
7.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "LO SPEED FAN
OFF" or "LO SPEED FAN ON" is displayed. This is the current setting for this feature. To toggle this
setting, perform steps 8) and 9). To keep this setting, proceed with step 10).
8.
To toggle this setting, press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons
simultaneously.
9.
"ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
10.
Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "NAG MINUTES = ##" or
"AUDIBLE NAG OFF".
11.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The
"NAG MINUTES =" portion of the display flashes.
12.
Press the FUNCTION SET YES (+) or NO (-) pushbutton until the value displayed equals the desired
audible alarm cutoff reset time period or "AUDIBLE NAG OFF", then release the pushbutton.
13.
Press and release the FUNCTION SET ENTER pushbutton.
14.
"ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The
display stops flashing.
15.
Press and release the FUNCTION SET DOWN arrow pushbutton to display "TEST/EQ HRS = ##".
16.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The
"TEST/EQ HRS =" portion of the display flashes.
17.
Press the FUNCTION SET YES (+) or NO (-) pushbutton until the value displayed equals the desired
timed test/equalize period.
NOTE!
To disable the manually initiated timed test/equalize feature, press the FUNCTION SET YES (+)
pushbutton until the value goes above 99. "TEST/EQ MAN STOP" is then displayed.