TLS-450 Setup and Operation Screens Manual
66
Pump Threshold (%)
This feature is for line manifolded tanks and is only enabled when you have the Dispense Mode set to
Manifolded:Sequential (See Setup/Pumps and Lines/Lines). When the tank's volume drops below the
entered Pump Threshold percentage, pumping will switch over immediately to the next available tank in
the line manifolded set. Pumping will continue from the current tank for another 10 seconds to avoid a
disruption in dispensing during the switch over.
Allowable entry: 0.00 to 50.00% (of the tank's full volume)
Default: 10.00%
Stick Offset Fuel
Allowable entry: -144 to +144 in (-3657.60 to 3657.60 mm)
Default: 0
Stick Offset Water
Allowable entry: -144 to +144 in (-3657.60 to 3657.60 mm)
Default: 0
Delivery Delay
Enter the number of minutes to wait after the Console determines that a Delivery is complete.
This delay period can prevent false Alarms and Warnings due to turbulence in the Tank caused by
Deliveries.
Allowable entry: 1 to 99 minutes
Default: 1
Gross Test Fail
The Gross Test Fail feature allows you to disable or enable an alarm that triggers when a 3.0 gph
(11.3lph) leak test fails.
Allowable selections: Enabled or Disabled
Default: Enabled
Periodic Test Fail
The Periodic Test Fail feature allows you to disable or enable an alarm that triggers if a 0.2 gph (0.76lph)
leak test fails.
Allowable selections: Enabled or Disabled
Default: Enabled
Annual Test Fail
The Annual Test Fail feature allows you to disable or enable an alarm that triggers when an 0.1 gph
(0.38lph) leak test fails.
Allowable selections: Enabled or Disabled
Default: Disabled