TLS-450 Setup and Operation Screens Manual
274
•
Meter-map - not complete - Set when any dim events received and one of the tanks is not
mapped. All tanks will be set.
•
Meter-map - unstable/changes during period - Any time the meter map table is changed (reset,
clear, unlock, lock, mapped). All tanks will be set.
•
Invalid fuel height - When an 'Invalid Fuel Height' is triggered. Set per individual tank.
•
Probe-out - When a 'Probe Out Alarm' is triggered. Set per individual tank.
•
Water removed - Check at Daily /Shift close time. Set when the water height from the previous
close is greater then the current water height. Set per individual tank.
•
Power outage - Always get set on power up or system reset. All tanks will be set.
•
Tank Chart Change (indicate what tank chart is used, and its quality level) [set per tank] - Check
at Daily /Shift close time.
Set when the time of the tank chart from the previous close is different from the current recorded
time. Set per individual tank.
•
DIM Queue Over Run - When we are receiving more Dim events then can be handled. All tanks
will be set.
Control Buttons (on right side of screen)
Manual Clear
Touching the 'Manual Clear' button causes the 'Confirm Manual Clear' dialog to display in which you can
clear the events from the screen.